What Is an Arc Flash Sensor? How It Works, Installation Locations, and Applications in Switchgear Arc Flash Protection

Date: September 29, 2026, 08:59:04

An arc sensor is a key component in the arc protection system of a switchgear cabinet, used to rapidly detect arc light signals. When an arc-induced short circuit occurs in the busbar compartment, circuit breaker compartment, or cable compartment, the sensor detects the intense light signal generated instantaneously and transmits the signal via optical fiber to the arc protection device. The protection device then rapidly issues a trip command based on arc criteria and optional fault current criteria.

Unlike solutions that rely solely on overcurrent protection, arc sensors are installed directly at locations prone to arc faults, helping the protection system identify the fault area more quickly. For low- and medium-voltage switchgear, busbar systems, cable rooms, capacitor cabinets, and certain power generation and industrial power distribution applications, arc detection serves as a critical means of rapid fault isolation.

  • Test Subject:The intense light signals generated by an arc fault, particularly the ultraviolet and blue light components.
  • Typical Installation Locations:Locations requiring monitoring for arc faults, such as the busbar compartment, switch compartment, and cable compartment of switchgear.
  • Transmission Method:After the probe captures the arc light signal, it is connected to the arc light detection module and the protection host via an optical fiber.
  • Protection Logic:Either the arc-flash single criterion or the arc-flash plus overcurrent dual criterion may be used.
  • Application Objectives:Reduce the time required to clear arc faults and minimize equipment damage and risks to personnel caused by the sustained release of arc energy.

InnoTechIF817 Arc Flash Protection DeviceMultiple arc flash sensors can be connected, and arc flash protection solutions for switchgear busbars, cable rooms, and multi-feeder systems can be developed by combining these sensors with current-based criteria.

I. What Is an Arc Light Sensor?

Arc Light Monitoring

An arc sensor is a device that detects light signals generated by arc faults inside electrical equipment.

When a short circuit occurs in a medium- and low-voltage switchgear, if an arc forms at the fault point, intense light radiation will be emitted from the fault area within a very short period of time. Arc sensors use optical probes to detect this abnormal light signal and then transmit the detection results to the arc protection device.

Once the arc-flash protection unit meets the set protection logic, it can quickly isolate the faulty power source via its trip output.

Therefore, a complete arc flash protection system typically includes:

  • Arc light probe;
  • Arc-light fiber;
  • Arc detection or photoelectric conversion module;
  • Arc-flash protection unit;
  • CT current signal;
  • Trip output circuit;
  • Communication and backend monitoring interfaces.

II. How do arc sensors detect arc faults?

When an arc short circuit occurs, it produces a transient bright light that is far brighter than the normal ambient light inside the switchgear, and it contains significant ultraviolet and visible light components.

Arc sensors capture light signals using specially designed optical probes. Taking the IF017 series sensors used in the IF817 arc protection system as an example, the system can employ full-spectrum probes or ultraviolet probes to detect abnormal arcs based on the spectral range being monitored.

The testing process can be summarized as follows:

  1. An arc-induced short circuit occurred inside the switchgear;
  2. The arc light sensor detected abnormal light radiation;
  3. Light signals are transmitted through arc-light optical fibers;
  4. The IF118 arc light module completes the photoelectric conversion;
  5. The protection device determines whether the light intensity exceeds the set threshold;
  6. If a dual-criterion approach is used, it is also necessary to determine whether the fault current meets the specified condition;
  7. When the protection logic is satisfied, a trip signal is output;
  8. Trip the corresponding circuit breaker to isolate the fault area.

III. Why Do Arc Sensors Use Fiber-Optic Transmission?

The interior of a switchgear cabinet is subject to a strong electromagnetic environment; in particular, during short circuits, arcing, and at the moment of switch operation, significant electromagnetic interference may occur.

Arc sensors use optical fibers to transmit light signals, thereby avoiding the need to transmit conventional electrical signals directly over long distances at the sensing end, which helps improve the system’s immunity to interference in complex electromagnetic environments.

The arc sensors in the IF817 application solution utilize non-electrical signal transmission via optical fiber and can be used in arc protection applications related to transformers, inverters, cables, and power generation equipment.

IV. What are the components of an arc sensor?

The IF017+IF118 series arc sensors used in the IF817 system primarily consist of the following components:

1. Arc Light Probe

Installed in the areas that actually require monitoring, it is used to capture the light signals generated by an arc.

Depending on the application, you can choose between a full-spectrum probe and a UV probe.

2. Arc-lit fiber

Used to transmit the optical signals collected by the probe to the arc light module; the length of the optical fiber can be configured based on the actual cabinet and installation location.

3. IF118 Arc Light Module

It is used to convert optical signals into electrical signals and to provide the detection results to the arc flash protection host for logical evaluation.

V. What is the difference between full-spectrum arc sensors and UV arc sensors?

Different arc light sensors can have different spectral detection ranges.

sports event Full-Spectrum Probe UV Probe
Typical models IF017A IF017C
Response Spectrum 280 nm–700 nm 280 nm to 400 nm
Detection range Covers ultraviolet and part of the visible spectrum Mainly detects the ultraviolet spectrum
Visible-light response A corresponding response exists Designed not to respond to visible light
main application Comprehensive Arc Light Spectral Analysis Arc Detection Requiring Reduction of Interference from Ordinary Visible Light

The choice of sensor should not be based solely on the principle that “higher sensitivity is always better”; instead, it should be determined by taking into account the lighting conditions inside the cabinet, the protection logic, and whether overcurrent is used as an auxiliary criterion.

VI. What is the detection angle of the arc sensor?

The arc light does not necessarily strike the sensor head-on, so the probe’s angular response characteristics are very important.

The IF017 series arc sensors feature an optical lens structure, and the detection angle range specified in the manual exceeds240°...which can expand the coverage area of a single probe within the cabinet.

However, a “wide detection angle” does not mean that a single sensor can cover the entire switchgear.

Switchgear is typically divided by metal partitions into:

  • Busbar Room;
  • Circuit breaker room or switch room;
  • Cable Room;
  • Instrument Room.

Metal partitions block the propagation of arc light; therefore, in actual design, arc light sensors should still be arranged appropriately based on the structure of each compartment and the fault areas that need to be protected.

VII. Where should arc sensors be installed?

Arc sensors cannot simply be installed anywhere inside the cabinet; their installation location directly affects the arc protection system’s ability to quickly detect faults.

1. Busbar Room

The busbar room is a critical monitoring area for arc flash protection.

When the busbar room arc sensor detects a fault arc, it generally indicates a busbar-side fault, requiring the rapid isolation of the corresponding busbar feeder or sectionalizer in accordance with the system protection scheme.

2. Switch Room or Circuit Breaker Room

Switch mechanisms, contacts, and connection points are also locations where arcing faults can occur.

Since faults occurring at different locations within the same circuit breaker room may correspond to different fault zones, the protection output must be designed in conjunction with the primary system configuration.

3. Cable Room

Arc faults can also occur near cable joints, connection terminals, and cable terminations.

When an arc sensor is installed separately in a cable room, it can trigger the circuit breaker for the corresponding bay according to the protection logic, thereby isolating the fault in that bay.

VIII. Why is it best to install arc detectors separately in the busbar room and the cable room?

This is because the protection coverage for the two types of faults is typically different.

Monitoring Area Typical Failure Scenarios Protection Strategy
Busbar Room Busbar-side fault It is usually necessary to disconnect the corresponding busbar feeder or section of the power supply.
Switch Room This may involve the busbar side or the bay side. Outputs Based on Single-Line Diagrams and Fault Zone Configuration
Cable Room Fault on the cable side within this section The circuit breaker in this compartment is usually the first to be tripped.

Therefore, arc-flash protection design is not merely about “tripping the circuit breaker when light is detected”; it must also address the following:

  • Where does the arc occur?;
  • Which circuit breaker should trip;
  • Is it necessary to expand the tripping range?;
  • How to prevent a problem from getting worse;
  • How to minimize the scope of unnecessary power outages.

IX. Why is an overcurrent criterion included in arc-flash protection?

Since arc sensors essentially detect light, when relying solely on light-based criteria, it is necessary to consider the possibility of false alarms caused by other strong light sources.

For example, strong natural light, lightning, or high-intensity flashlights used during on-site maintenance may cause the light sensor to receive strong light signals.

Therefore, arc flash protection systems commonly use:

Arc Flash Signal + Fault Current

Implement dual-criterion protection.

The system will only issue a trip command when both the arc intensity meets the set criteria and the fault current meets the protection criteria.

The IF817 supports dual criteria (arc flash and overcurrent) and also allows for the selection of arc flash as the sole criterion based on project requirements. The actual protection scheme should be set up according to the system’s primary wiring, protection coordination, and operational requirements.

ferret outIF817 Arc Flash Protection Device: Technical Specifications and Application GuidelinesThe

10. How do I set the activation threshold for the arc light sensor?

Arc sensors should not simply be set to “the more sensitive, the better.”

Setting the sensitivity too low may increase the risk of interference from ambient light, while setting it too high may reduce the ability to detect actual arc faults.

The IF817 Arc Flash Protection System manual describes the adjustable arc flash trip threshold feature, which allows the thresholds for certain arc flash channels to be configured based on the on-site lighting conditions and protection requirements.

The arc sensitivity range specified in the device's technical specifications is:

  • 1–15 mW/cm²;
  • Or 1–20 kLUX.

Actual calibration cannot be conducted in isolation from on-site conditions; it should take into account:

  • Sensor Type;
  • Fiber length;
  • Normal ambient light inside the cabinet;
  • Arc light probe installation location;
  • Single criterion or dual criterion;
  • Actual debugging and testing results.

Confirm.

XI. How fast is the arc sensor’s response time?

One of the benefits of arc flash protection is its speed.

The duration of energy release during an arc fault is very brief; if the protection trip time is too long, it may increase the extent of equipment damage.

As stated in the IF817 Arc Flash Protection Device ManualThe typical total response time is 7 ms.The

It is important to note that the total fault clearance time also includes the tripping time of the external circuit breaker itself; therefore, the response time of the arc protection device and the circuit breaker’s operating time are two distinct concepts.

12. How many arc sensors can be connected to a single arc protection device?

For switchgear systems with multiple cabinets or compartments, the number of arc-light input channels is a very important parameter to consider during selection.

The IF817 arc flash protection device supports:

  • 32-channel arc light input;
  • Equipped with expansion interfaces;
  • When expanded, it can support up to 64 Arc Light channels.

Therefore, during the project design phase, you can start by compiling statistics on:

  • Number of switchgear cabinets;
  • The number of compartments to be monitored per cabinet;
  • Number of busbar sections;
  • Number of incoming lines;
  • Is a cable room required for protection?;
  • Will future expansion be necessary?

Next, determine the actual number of arc channels.

13. How should arc-flash protection be configured for double-feed switchgear?

For switchgear systems with dual feeders, dual busbars, or a bus tie, arc flash protection cannot simply connect all sensors to a single trip output.

The IF817 provides 6 current inputs and supports either a single-input or dual-input configuration.

A dual-feed system can be based on:

  • Incoming Line I Current;
  • Incoming Line II Current;
  • Busbar I arc zone;
  • Busbar II arc zone;
  • Parent-child relationship;
  • Corresponding arc sensor channel;
  • Different trip outputs.

Establish a partition protection logic.

This ensures that, while maintaining fast protection response times, the tripping zone matches the actual fault area as closely as possible.

14. What should be kept in mind when installing an arc light sensor?

According to the IF817 installation instructions, the arc detection probe should be installed at the actual monitoring location, such as busbar rooms, cable rooms, and other areas.

During installation, we recommend paying special attention to the following:

  1. The sensor's field of view must not be completely obstructed by metal plates or other components;
  2. The probe should be oriented to cover the areas where arcing is most likely to occur;
  3. Separate metal compartments should be provided for different metals based on protection requirements;
  4. Avoid excessive bending of fiber-optic cables;
  5. The connections between the probe, the optical fiber, and the arc light module are reliable;
  6. Check the channels and protection logic after the host installation is complete;
  7. An arc circuit test must be performed before official commissioning.

15. Can the optical fiber of an arc light sensor be bent freely?

Not recommended.

If the bending radius of an optical fiber is too small, it may increase signal transmission loss; in severe cases, it may even damage the fiber.

The minimum fiber bend radius specified in the IF817 sensor test conditions is25 mmThe

When actually running the cables, you should also avoid:

  • Sharp-angle bend;
  • Pinned between cabinet doors;
  • Compressed by fasteners;
  • Friction with moving mechanical parts;
  • Vigorous pulling during construction.

16. How do you test the arc flash protection system after installation?

Completion of installation does not mean that the system is already capable of providing reliable protection; circuit and functional testing must be completed before the system is put into full operation.

To test the arc-flash circuit, a dedicated simulated arc-flash test light source or a compliant ultraviolet test light source can be used to illuminate the sensor probe to verify whether the protective device can correctly identify the corresponding arc-flash channel.

During debugging, we recommend verifying the following separately:

  • Are the arc channel numbers correct?;
  • Correspondence between probes and host channels;
  • Is the arc flash alarm functioning properly?;
  • Whether the overcurrent criteria are correct;
  • Is the logic for the trip output correct?;
  • Has the alarm relay tripped?;
  • Is RS485 uploading information correctly?;
  • Does the system return to normal after the arc light disappears?

If the protection uses both arc and overcurrent criteria, the trip logic for the arc criterion, the overcurrent criterion, and the combination of both must be verified separately.

17. How is the arc flash protection device connected to the backend monitoring system?

In addition to triggering a rapid trip on-site, the arc flash protection system can also upload protection status and alarm information to the backend.

The IF817 is equipped with two EIA-485 communication interfaces that use the Modbus RTU protocol, which can be used to read device status and related protection information.

Its communication parameters include:

  • 2 EIA-485 interfaces;
  • Modbus RTU;
  • Multiple communication baud rates;
  • Use shielded twisted-pair cable for the wiring;
  • Configure the communication range according to the instructions in the manual.

This allows arc-flash protection to be integrated into the comprehensive online monitoring system for substations or industrial power distribution.

XVIII. Which types of equipment are suitable for installing arc sensors?

The typical applications described in the IF817 manual include a variety of scenarios involving medium- and low-voltage electrical equipment.

These primarily include:

  • Medium-Voltage Switchgear;
  • Low-voltage switchgear;
  • Busbar system;
  • Cable Room;
  • Low-voltage capacitor cabinet;
  • Power plant busbar and cable systems;
  • Electrical equipment related to wind power generation;
  • Power Distribution Systems in Industrial Enterprises.

The number of sensors, their installation locations, and the trip logic in different applications should be determined based on the actual configuration of the primary system.

19. What is the difference between an arc light sensor and a standard light sensor?

An arc light sensor is not simply a standard illuminance sensor.

It focuses more on the characteristic spectra of arc faults, transient light intensity, and rapid coordination with protection systems.

When selecting equipment for a project, you should focus on the following:

  • Spectral response range;
  • Detection angle;
  • Arc detection sensitivity;
  • Response time;
  • Resistance to ambient light interference;
  • Fiber-optic transmission methods;
  • Ensure host compatibility;
  • Does it support overcurrent auxiliary criteria?;
  • On-site testing method.

20. What parameters need to be confirmed when selecting an arc light sensor?

If you need to configure or retrofit the arc flash protection system for a switchgear, we recommend providing the following information before requesting a quote:

  • Number of switchgear cabinets;
  • Voltage class;
  • A system diagram;
  • Single-feed or dual-feed;
  • Is there a master link?;
  • Do you need to monitor the busbar room, switch room, or cable room?;
  • Estimated number of arc sensors;
  • The approximate distance between the sensor and the host;
  • CT secondary rated current;
  • Circuit Breaker Trip Requirements;
  • Is RS-485 communication required?;
  • Backend System Communication Requirements.

If your project requires a complete arc flash protection system—including a control unit, arc flash sensors, fiber optics, and a trip mechanism—please seeIF817 Arc Flash Protection Device and Switchgear Arc Flash Protection SystemThe

21. Frequently Asked Questions (FAQ) About Arc Sensors

Where are arc sensors typically installed in switchgear?

Common installation locations include busbar rooms, switch rooms, and cable rooms. The specific number and installation locations should be determined based on the cabinet compartment structure and the scope of protection.

Does a switchgear cabinet require only one arc sensor?

Not necessarily. Because there are metal partitions inside the switchgear, arcs between the busbar compartment, switch compartment, and cable compartment may not be effectively covered by a single probe; therefore, the configuration should be based on the actual compartments and protection targets.

Can an arc light sensor trip the circuit breaker immediately just by detecting light?

An arc-light-only detection criterion can be designed, but when using the arc-light criterion alone, the possibility of false trips caused by other strong light sources must be considered. The IF817 supports a dual detection criterion combining arc light and overcurrent; the manual recommends using the current-based auxiliary criterion to enhance protection reliability.

Will an arc light sensor trigger when detecting ordinary lighting?

Whether the sensor triggers depends on the probe type, spectral range, and trigger threshold. UV probes can reduce the influence of ordinary visible light, while full-spectrum probes should be used in conjunction with appropriate thresholds and auxiliary overcurrent detection criteria.

Do arc sensors use cables or fiber optics for signal transmission?

The IF817-compatible arc light sensor uses optical fibers to transmit the detected light signals, which are then converted into electrical signals by the IF118 arc light module.

What is the maximum number of arc sensors that can be connected to the IF817?

The host supports 32 ArcLight inputs and can accommodate up to 64 ArcLight inputs via expansion.

How fast does the arc flash protection respond?

The typical total response time of the IF817 arc protection device is 7 ms. The system’s final fault clearance time must also take into account the circuit breaker’s own tripping time.

How do I choose between full-spectrum and UV arc light probes?

Full-spectrum sensors cover a wider spectral range, while ultraviolet sensors primarily respond to ultraviolet light and minimize the influence of visible light. The choice should be determined based on a comprehensive evaluation of the on-site environment, the risk of false triggering, and the protection logic.

Which circuit breaker should trip after an arc occurs in the busbar room?

Busbar room faults are typically classified as busbar-side faults, and the protection logic generally requires the corresponding feeder or power section to be isolated. The specific trip logic should be determined based on the primary system wiring and protection scheme.

If an arc occurs in the cable room, does the entire busbar need to be tripped?

The typical configuration described in the manual treats an arc in the cable compartment as a fault within that bay; the arc protection trip output can be connected to the corresponding bay circuit breaker to isolate the fault. In actual projects, however, the specific configuration must still be determined based on the system design.

22. IF817 Arc Flash Protection Device and Arc Flash Sensor Solution

The Innotongda IF817 arc flash protection device can be used in conjunction with the IF017 series arc flash sensors, arc flash fiber optics, and the IF118 arc flash module to build arc flash protection systems for medium- and low-voltage switchgear, busbars, cable rooms, and industrial power distribution equipment.

Key configuration features include:

  • 32-channel arc light input;
  • Expandable to up to 64 arc lights;
  • Supports both arc flash and overcurrent detection criteria;
  • 6-channel current input, supporting single-line or dual-line configurations;
  • Typical total response time: 7 ms;
  • Full-spectrum and UV arc light probes are available;
  • Multi-channel trip output;
  • SOE event log;
  • Dual-channel EIA-485 communication;
  • Supports Modbus RTU.

If you need to design arc flash protection for new switchgear or retrofit arc flash protection for existing distribution panels, please provide the primary system diagram, the number of cabinets, the busbar sectioning method, the arc flash monitoring locations, and the trip requirements. Innotongda will then assist in determining the number of arc flash sensors, their installation locations, and the IF817 protection configuration.

Product Information:IF817 Arc Flash Protection Device

Note: The technical data for the IF817, IF017, and IF118 in this document is compiled based on the product manuals. The number of sensors, protection settings, CT configuration, trip outputs, and protection logic for actual projects should be confirmed based on the primary system, protection coordination, and project technical requirements.