IB-K201 Dry-type transformer thermostatModel Selection Instructions
model number | functionality |
IB-K201D | Three-phase circuit display/maximum value display; fan automatic/manual start/stop; over-temperature alarm; over-temperature trip; fault alarm; "black box" function; Fan timed excitation function; analog test function; digital compensation function; cabinet door open alarm function. |
IB-K201E | Conventional functions are the same as the IB-K201D model, with the addition of three or four independent 4-20mA analog current outputs. |
IB-K201F | Conventional functions are the same as IB-K201D model, with the addition of RS485/232 serial communication function. |
IB-K201G | Conventional functions are the same as IB-K201D, with the addition of a way to measure and control the ambient temperature of the computer room. |
IB-K201I | Conventional functions are the same as IB-K201D, with the addition of a transformer core temperature measurement and alarm. |
IB-K201H | Conventional functions are the same as IB-K201D, with the addition of one way humidity measurement and control. |
IB-K201L | Conventional functions are the same as those of IB-K201D, with the addition ofCooling FansFault detection and alarm. |
IB-K201C | Conventional functions are the same as IB-K201D model, with the addition of thermistor PTC150 or PTC130 for interlocking control. |
IB-K201TH | Conventional functions are the same as IB-K201D type, with triple-proof measures against mold, humidity and salt spray. |
(For more features contact us for the latest details)
Remarks:
1, IB-K201F, K for medium-sized wall-mounted temperature control box, 2 for AC220V power supply/3 for AC380V power supply, F for function code (RS485 communication)
2、Function code can be combined according to the demand, the order is E, F, G, I, L, H, C, P, N, TH, if only L, H, C, P, N, TH function, need to add D in front of the code.
3, if there are other special technical or functional requirements, such as Ethernet communication, Profibus communication, multi-channel temperature measurement, fiber optic temperature measurement, etc., can contact us.
IB-K201 Dry-type transformer temperature controller technical indicators
Ambient temperature. | -20℃~+55℃ |
Ambient humidity. | < 95% (25°C) |
Operating Voltage. | AC 220V (+10%, -15%) |
Operating Frequency. | 50Hz or 60Hz (±2Hz) |
Measuring range. | -30.0℃~240.0℃ |
Measurement Accuracy:: 1 | ±1%FS (thermostat class 0.5, sensor class B) |
Resolution. | 0.1°C |
Fan Output Capacity. | 9A/250VAC |
Control output capacity. | 5A/250VAC; 5A/30VDC (resistive) |
Thermostat power consumption. | ≤8W |
Production Standard. | JB/T7631-2016 "electronic temperature controller for transformer" industry standard |
Certified Standards. | ISO9001:2016 International Quality Management System Certification |
Adoption of test standards. | IEC 61000-4:1995 International Standard |
Adoption of technical standards. | GB/T17626-2008 Standard for Electromagnetic Compatibility Test and Measurement Techniques |