GIS Circuit Breaker Operational Characteristics Online Monitoring System
IN-309G GIS Circuit Breaker Action Characteristics Online Monitoring System

System Introduction
IN-309G GIS Circuit Breaker Operational Characteristics Online Monitoring SystemIt is one of the monitoring technology solutions for GIS equipment, aiming at real-time monitoring of the action characteristics of GIS circuit breakers, such as opening and closing time, speed and stroke, and other key parameters, to ensure the reliable operation of the power system. The system consists of high-precision sensors, data acquisition and processing module, communication module, power supply module and background monitoring and diagnostic analysis software.
System Selection
serial number | Diethylammonium chloride | Product Model |
---|---|---|
1 | Three-phase linkage GIS circuit breaker action characteristic on-line monitoring system | IN-309GS |
2 | Three-phase split GIS circuit breaker action characteristic on-line monitoring system | IN-309GD |
Equipment parameters
Closing and opening time accuracy | ≤0.1ms | Speed measurement accuracy | ≤±0.5m/s |
Stroke Measurement Accuracy | ≤±0.5mm | Sensor Response Time | ≤±1ms |
Current Sampling Accuracy | 1% | Closing and opening current range | 0 to 25A |
IED Sampling Frequency | ≥10kHz | Energy storage current range | 0 to 50A |
Waveform sampling accuracy | 0.1% | communication interface | Serial, Ethernet or Wireless |
environmental adaptation | Ambient temperature: -40℃~+70℃; Ambient humidity: 0~95% (no condensation) | ||
Operating power | IED monitoring unit: AC220V, ±10%; sensor: DC24V, ±10% |