Dry-type transformer crossflowCooling FansGFDD470-150 GFDD470-110 GFDD470-90 GFDD370-150 GFDD370-110 GFDD370-90 and other models, manufacturers of general, reasonable price, the specific price of the contact phone: 400-181-6499

GFDD series top-blowing dry-type transformer with cross-flow cooling fan (hereinafter referred to as: dry-type transformer cross-flow cooling fan) is mainly used for dry-type transformer cooling to increase capacity, and electronic equipment, distribution cabinets, high and low voltage switchgear and other forced air cooling. Dry-type transformer with this fan cooling, can increase capacity 40 ~ 50% operation, thus greatly improving the carrying capacity of dry-type transformer, and extend the service life of the dry-type transformer, is the domestic and foreign manufacturers commonly used economic and effective way.

This product is designed and produced strictly according to JB/T8971-1999 "Cross-flow cooling fan for dry-type transformer". Motor stator and rotor core adopts high quality cold rolled silicon steel sheet; low noise bearing; impeller adopts aluminum alloy surface electrophoresis treatment, and then through the fine dynamic balance adjustment; left and right end plate adopts stainless steel plate stamping molding, wind inlet plate, wind plate and wind guiding plate adopts aluminum alloy profiles buckle combination; the whole fan structure is reasonable, beautiful modeling, has a large air volume, low noise, low temperature rise, long service life, smooth running, easy to install and so on. The whole fan has a reasonable structure and beautiful shape.

Some models show More models contact us for inquiry
GFDD470-110
GFDD470-120
GFD470-110
GFD470-120
GFDD470-150
GFDD470-155
GFD470-150
GFD470-155
GFDD590-110
GFDD590-120
GFD590-110
GFD590-120
GFDD590-150
GFDD590-155
GFD590-150
GFD590-155
GFDD440-110
GFDD440-120
GFD440-110
GFD440-120
GFDD440-90
GFD440-90
GFDD1050-120/110
GFDD1100-120/110
GFDD1200/120/110
GFDD1250-120/110
GFDD1300-120/110
GFDD1400-120/110
GFDD1300-120 
GFDD1400-120 
GFDD1500-120 
GFDD1600-120 
GFDD1700-120 
GFDD1430-120 
GFDD1240-120/110
GFDD/GFD1300-108
GFDD1340-120/110
GFDD1500-120/110 
GFDD1120-120/110

Example: GFDD470-150: indicates single-phase 220V, fan total length of 470mm, impeller diameter of 150mm top blowing dry-type transformers with cross-flow cooling fan

 Dry-type transformer cooling fan model Performance parameters

Model Specification Motor parameters air volume
(m³/h)
static (in a signal)
dB(A)
Transformer capacity Number of units
Voltage (V) phase (math.) frequency
(Hz)
Current (A) power (output)
(W)
number of revolutions per minute
(r/min)
GFD(s) D370-120 220/380 Single/Triple 50 0.24/0.15 45 1400 700 <50 315-500 6
GFD(s) D385-120 220/380 Single/Triple 50 0.24/0.15 45 1400 710 <50 315-500 6
GFD(s) D420-120 220/380 Single/Triple 50 0.24/0.15 50 1400 720 <50 400-800 6
GFD(s) D440-120 220/380 Single/Triple 50 0.24/0.15 50 1400 750 <50 400-1000 6
GFD(s) D470-120 220/380 Single/Triple 50 0.24/0.15 50 1400 810 <50 800-1250 6
GFD(s) D490-120 220/380 Single/Triple 50 0.24/0.15 50 1400 850 <50 1000-1600 6
GFD(s) D520-120 220/380 Single/Triple 50 0.25/0.15 55 1400 870 <50 1250-1600 6
GFD(s) D560-120 220/380 Single/Triple 50 0.25/0.15 55 1400 900 <50 1250-2000 6
GFD(s) D590-120 220/380 Single/Triple 50 0.25/0.15 55 1400 950 <50 2000-2500 6
GFD(s) D610-120 220/380 Single/Triple 50 0.28/0.16 60 1400 1000 <50 2000-2500 4
GFD(s) D700-120 220/380 Single/Triple 50 0.28/0.16 60 1400 1150 <52 2000-2500 4
GFD(s) D760-120 220/380 Single/Triple 50 0.28/0.16 60 1400 1300 <52 2000-2500 4
GFD(s) D780-120 220/380 Single/Triple 50 0.28/0.16 60 1400 1360 <52 2000-2500 4
GFD(s) D810-120 220/380 Single/Triple 50 0.28/0.16 60 1400 1400 <52 2000-2500 4
GFD(s) D850-120 220/380 Single/Triple 50 0.28/0.16 60 1400 1430 <52 2000-2500 4
GFD(s) D920-120 220/380 Single/Triple 50 0.34/0.19 80 1400 1500 <55 2000-2500 2
GFD(s) D1020-120 220/380 Single/Triple 50 0.34/0.19 80 1400 1600 <55 2000-2500 2
GFD(s) D1120-120 220/380 Single/Triple 50 0.35/0.20 80 1400 1700 <56 2000-2500 2
GFD(s) D1200-120 220/380 Single/Triple 50 0.40/0.20 85 1400 1800 <56 2000-2500 2
GFD(s) D1220-120 220/380 Single/Triple 50 0.40/0.20 85 1400 1850 <56 2000-2500 2
GFD(s) D1300-120 220/380 Single/Triple 50 0.40/0.20 85 1400 1900 <56 2000-3000 2
GFD(s) D1400-120 220/380 Single/Triple 50 0.40/0.20 95 1400 2400 <57 2000-3000 2
GFD(s) D370-150 220/380 Single/Triple 50 0.28/0.16 60 1400 850 <54 630-800 6
GFD(s) D420-150 220/380 Single/Triple 50 0.28/0.16 80 1400 900 <55 800-1600 6
GFD(s) D470-150 220/380 Single/Triple 50 0.28/0.16 80 1400 1200 <55 800-1600 6
GFD(s) D490-150 220/380 Single/Triple 50 0.28/0.16 80 1400 1300 <55 800-1600 6
GFD(s) D590-150 220/380 Single/Triple 50 0.38/0.24 90 1400 1500 <56 1600-2500 6
GFD(s) D650-150 220/380 Single/Triple 50 0.45/0.26 100 1400 1600 <56 2000-3000 6
GFD(s) D780-150 220/380 Single/Triple 50 0.50/0.29 110 1400 2000 <56 2500-3500 6
GFD(s) D850-150 220/380 Single/Triple 50 0.54/0.31 120 1400 2500 <56 2500-3800 6
GFD(s) D650-200 220/380 Single/Triple 50 1.4/0.5 320 1350 2500 <60 1600-2500 6
GFD(s) D780-200 220/380 Single/Triple 50 1.4/0.53 325 1350 3200 <60 3150-4000 6
GFD(s) D850-200 220/380 Single/Triple 50 1.7/0.75 370 1350 3500 <60 4000-5000 6
GFD(s) D900-200 220/380 Single/Triple 50 1.8/0.85 400 1350 3800 <60 5000-8000 6
GFD(s) D1180-200 220/380 Single/Triple 50 2.5/0.95 550 1350 4800 <60 8000-16000 6
GFD(s) D1300-200 220/380 Single/Triple 50 2.7/0.95 600 1350 5500 <60 16000-20000 6

How it works:

This series cooling fan is used in dry type transformer, the fan is placed on both sides of the lower part of the transformer coil, blowing the cold air directly into the coil of the transformer high and low pressure cooling air ducts, the heat dissipation effect is obvious, which can guarantee the normal operation of the transformer and prolong its service life. (Fan start, stop and transformer over-temperature alarm, over-temperature tripping and other functions are provided by the temperature control device).