BWDK-326 Temperature Controller Model and Function
Date: July 10, 2025 08:34:05
model number | Functional Description |
---|---|
BWDK-326D(regular type) | Three-phase circuit measurement and display; input open circuit and fault self-test display and output;Cooling FansAutomatic start-stop output; over-temperature alarm display and output; over-temperature trip display and output; fan manual/automatic control of the two state display, output and mutual switching; digital compensation of the display value of each channel; "black box" function; fan timing start-stop control function; output state detection. |
BWDK-326E | Same as D-type, with the addition of three independent 4~20mA analog current outputs. |
BWDK-326F | Same as D type, with added RS-485 serial communication function. |
BWDK-326G | Same as type D, with one additional way of measuring and controlling the ambient temperature of the machine room. |
BWDK-326I | The same as D type, adding a transformer core temperature measurement and alarm. |
BWDK-326EF | On the basis of D type, RS-485 communication function and 4~20mA analog current output are added at the same time. |
Key functional features:
-
Temperature monitoring and controlReal-time monitoring of three-phase winding temperature, automatic start and stop cooling fan, over-temperature alarm and trip protection.
-
communication function: Some models (e.g. F-type, EF-type) support RS-485 communication interface and Modbus protocol to realize remote data transmission and centralized management.
-
analog output: Some models (e.g., E-type, EF-type) provide 4~20mA analog current output, which is convenient for remote monitoring system integration.
-
black box function: Record the temperature and equipment status at the moment of power failure for easy fault analysis.
-
Sensor Failure Detection: Supports sensor open circuit and short circuit detection, and displays the fault phase and type.
-
anti-interference design: Conforms to IEC61000-4 international standards and adapts to industrial complex environments.
-
Cooling fan automatic start/stop outputWhen the transformer winding temperature reaches the set fan start temperature, the temperature controller will automatically start the fan for forced air cooling; when the temperature drops below the set fan shutdown temperature, the fan will automatically stop.
-
Fan manual/automatic control switching: Users can manually control the start and stop of the fan through the panel buttons, or set it to automatic control mode to realize unattended operation.
-
Fan timer start/stop functionIn order to prevent the fan from rusting or clogging when it is not running for a long period of time, BWDK-326D also has the function of starting the fan at regular intervals, and the user can set the regular time so that the fan will run automatically for a certain period of time after it reaches the set time.
-
Wind turbine condition detection and protection: The thermostat detects fan operation status and sends an alarm signal in case of fan failure or sensor abnormality.