Dry-type transformer fans
Date: July 19, 2025 08:13:44

-
Cross-flow (GFDD series): single-phase 220 V, length 365-770 mm, impeller diameter 90-155 mm, power 25-90 W, air volume 570-1800 m³/h.
-
Top-blowing type: installed on the top of the transformer, the cold air is blown vertically downward, suitable for cabinets with narrow space.
-
Side-blowing type: installed on both sides of the lower part of the coil, with a horizontal angle of 135 °, the cold air is blown directly into the air ducts of the high and low voltage coils, the most commonly used.
Transformer capacity (kVA) | Recommended Models | Quantity per unit | Air volume (m³/h) | Power (W) |
---|---|---|---|---|
315-630 | GFDD365-120 | 4-6 | 580 | 40 |
800-1600 | GFDD470-120 | 4-6 | 750 | 60 |
1600-2500 | GFDD590-120 | 6 | 950 | 60 |
2500-3150 | GFDD690-120 | 6 | 1050 | 60 |
3150-5000 | GFDD770-150 | 6 | 1800 | 90 |
-
Position: either side of the clip under the coil, or top, with the air outlet aligned with the coil air duct.
-
Angle: Side-blown blades approximately 135° from horizontal, top-blown vertically downward.
-
Fixing: foot support + rubber damping pads to ensure no resonance; air inlet ≥20 cm from obstacles.
-
Wiring: fan power line and thermostat fan terminals (normally open contact 10 A/250 VAC) are directly connected in series; the fan automatically stops after the thermostat is powered down, meeting the requirements of fire linkage.
- Start: Winding temperature ≥ "Ob(set) + dF(return difference)".
- Stop: Winding temperature ≤ "Ob - dF".
- Timed self-check: automatic start/stop for 2 min every 24 h to prevent bearing stalling (can be turned off).
- Manual: "Manual/Auto" key on the panel switches; manual start requires the temperature to drop below the return difference before automatic reset.
-
Power supply: L → thermostat fan terminal 11 → fan L; N → fan N.
-
Standby: Fire cut relay normally closed contacts are strung into the fan power supply to force the fan to stop in case of fire.
- Monthly: Clean ash, check for blade deformation, loose fasteners.
- Every six months: measured vibration ≤ 4.5 mm/s; noise ≤ 55 dB(A).
- Annually: Measure insulation resistance ≥ 2 MΩ; thermostat fan output contacts on and off test.
"For dry transformers with a capacity of ≤ 1600 kVA, 4-6 sets of GFDD470-120 cross-flow fans are routinely installed, which can be started and stopped automatically by a thermostat; for larger capacities or high ambient temperatures, the fans can be connected in parallel with a redundant fan or changed to a top-blowing type, and the design of the ventilation ducts can be strengthened."