Online gas monitoring system for transformer oil with few components
IN-201C OMS for DGA in Transformer Oil with Few Components
♦ (chemistry)System Introduction
IN-201C less-component oil chromatography is mainly used to measure and analyze trace gases in insulating oil: hydrogen H2, carbon monoxide CO, acetylene C₂H₂, ethylene C₂H₄, etc. Measurement of micro-water and iron core can also be integrated. The human-machine interface can be selected from LCD liquid crystal or digital tube to capture potential fault information in real time and ensure reliable operation of the transformer. It is suitable for power plants, substations, traction stations, special transformers and other 110kV and below oil-immersed transformers, and is also used for train on-board transformers.
♦ (chemistry)System Features
☆ Compact size, wall-mounted one-piece structure, can be installed directly at the transformer oil valve.
☆ No need for regular carrier gas replacement, full life cycle maintenance free.
♦ (chemistry)Equipment parameters
Measurement type | H₂, CO, C₂H₂, C₂H₄ | Optional Features | Microwater/core/clamp/oil temperature/oil pressure |
Degassing method | Nano-ceramic degassing | pressure resistance | 0 ~ 0.6 MPa |
Monitoring Principles | electrochemical | Overall dimensions | 325 × 230 × 217 mm |
altitude | ≤ 5000 m | protection class | IP55 |
Mainframe power supply | AC220V ±10% | communication protocols | Modbus or DL/T860 |
environmental adaptation | Ambient temperature: -40℃ ~ +70℃; Ambient humidity: 0 ~ 95% (no condensation) | ||
Mechanical durability | 5 ~ 17 Hz, 0.1″ bimodal displacement; 17 ~ 640 Hz, 1.5 G peak-to-peak acceleration; wind speed ≤ 35 m/s |