BWDK-Q201 Dry-type transformer thermostat Model Selection Instructions
model number | functionality |
BWDK-Q201D | Three-phase circuit display/maximum value display; fan automatic/manual start/stop; over-temperature alarm; over-temperature trip; fault alarm; "black box" function; Fan timed excitation function; analog test function; digital compensation function; cabinet door open alarm function. |
BWDK-Q201E | Conventional functions are the same as BWDK-Q201D, with the addition of 4-20mA analog current output. |
BWDK-Q201F | Conventional functions are the same as BWDK-Q201D, with the addition of RS485/232 serial communication function. |
BWDK-Q201G | Conventional functions are the same as BWDK-Q201D, with the addition of a way to measure and control the ambient temperature of the computer room. |
BWDK-Q201I | Conventional function is the same as BWDK-Q201D type, increase all the way transformer core temperature measurement and alarm. |
BWDK-Q201C | Conventional functions are the same as BWDK-Q201D, with the addition of thermistor PTC150 or PTC130 for interlocking control. |
(For more features contact us for the latest details)
Remarks:
1, such as: BWDK-Q201F dry-type transformer thermostat, BWDK on behalf of the thermostat national standard model, Q on behalf of inlaid iron shell thermostat, F is the code name of the communication function;
2, E, F, G, I, C are function codes, function codes can be combined, the following examples:
Thermostat model: BWDK-Q201FG, description is inlaid iron shell thermostat, its function includes: conventional function, communication function (F), and add all the way to the machine room environment temperature measurement and control function (G).
If there are already 2 functions such as E and F, and then add G and I functions, only one of them can be selected as an added function, and the maximum number of function codes that exist at the same time is 3. Examples of thermostat model numbers: BWDK-Q201EFG, BWDK-Q201EFI.
3, if there are other special technical or functional requirements, such as Ethernet communication, Profibus communication, multi-channel temperature measurement, fiber optic temperature measurement, etc., can contact us.
BWDK-Q201 dry-type transformer temperature controller technical indicators
Ambient temperature. | -20℃~+55℃ |
Ambient humidity. | < 95% (25°C) |
Operating Voltage. | AC 220V (+10%, -15%) |
Operating Frequency. | 50Hz or 60Hz (±2Hz) |
Measuring range. | -30.0℃~240.0℃ |
Measurement Accuracy:: 1 | ±1%FS (thermostat class 0.5, sensor class B) |
Resolution. | 0.1°C |
Fan Output Capacity. | 9A/250VAC |
Control output capacity. | 5A/250VAC; 5A/30VDC (resistive) |
Thermostat power consumption. | ≤8W |
Production Standard. | JB/T7631-2016 "electronic temperature controller for transformer" industry standard |
Certified Standards. | ISO9001:2016 International Quality Management System Certification |
Adoption of test standards. | IEC 61000-4:1995 International Standard |
Adoption of technical standards. | GB/T17626-2008 Standard for Electromagnetic Compatibility Test and Measurement Techniques |